Register Map addressing of Unitronics Vision V350 X Indusoft
MODBUS protocol (MODBU and MOTCP drivers)
  Description

Unitronics

Prefix

Qtd Range Offset
hexa
Offset
decimal

Modbus
Read
Write

Prefix

Read
Write

Modbus

read

Read
Start End Start End
1 Counter Current C 32 C0
C31
F000 61440 4X 4X:61441 4X:61472 3X 3X:61441 3X:61472
2 Counter Preset C 32 C0
C31
E000 57344 4X 4X:57345 4X:57376 3X 3X:57345 3X:57376
3 Double Word DW 256 DW0
DW255
8000 32768 DW DW:32769 DW:33024 DW3 DW3:32769 DW3:33024
4 Inputs I 12 I0
 I11
6000 24576 0X 0X:24577 0X:24588 1X 1X:24577 1X:24588
5 Memory bit MB 8192 MB0
MB8191
0 0 0X 0X:1 0X:8192 1X 1X:1 1X:8192
6 Memory Float MF 64 MF0
MF63
4000 16384 DW DW:16385 DW:16448 DW3 DW3:16385 DW3:16448
7 Memory Integer MI 4096 MI0
MI4095
0 0 4X 4X:1 4X:4096 3X 3X:1 3X:4096
8 Memory long ML 512 ML0
ML511
7000 28672 DW DW:28673 DW:29184 DW3 DW3:28673 DW3:29184
9 Saída O 12 O0
O11
4000 16384 0X 0X:16385 0X:16396 1X 1X:16385 1X:16396
10 System Bit SB 512 SB0
SB511
5000 20480 0X 0X:20481 0X:20992 1X 1X:20481 1X:20992
11 System Double Word SDW 64 SDW0
SDW63
B000 45056 DW DW:45057 DW:45120 DW3 DW3:45057 DW3:45120
12 System Integer SI 512 SI0
SI511
9000 36864 4X 4X:36865 4X:37376 3X 3X:36865 3X:37376
13 System Long SL 56 SL0
SL55
A000 40960 DW DW:40961 DW:41016 DW3 DW3:40961 DW3:41016
14 Timer Current T 384 T0
T383
D000 53248 DW DW:53249 DW:53632 DW3 DW3:53249 DW3:53632
15 Timer Preset T 384 T0
T383
C000 49152 DW DW:49153 DW:49536 DW3 DW3:49153 DW3:49536
16 X bit (high speed) XB 1024 XB0
XB1023
3000 12288 0X 0X:12289 0X:13312 1X 1X:12289 1X:13312
17 X DW (high speed) XDW 64 XDW0
XDW63
6000 24576 DW DW:24577 DW:24640 DW3 DW3:24577 DW3:24640
18 X Integer (high speed) XI 512 XI0
XI511
3000 12288 4X 4X:12289 4X:12800 3X 3X:12289 3X:12800
19 X Long (high speed) XL 256 XL0
XL255
5000 20480 DW DW:20481 DW:20736 DW3 DW3:20481 DW3:20736

Remarks
Row Detail
2 Presets the counter but returns the counter current value  
4 Read only
6 Returned value must be handled in the application
11 Several registers are read only
12 Most registers are read only
13 Most registers are read only


Source:
Indusoft Modbu - Driver version 10.9 bundled with Indusoft WebStudio
Visilogic Function Blocks V230-21-G23 Rev: 3:00